MMG 130 Interim Tier 4 Mobile Generator

The MMG 130 is powered by a John Deere PowerTech engine which utilizes a catalyzed exhaust filter that contains a Diesel Oxidation Catalyst (DOC) and a Diesle Particulate Filter.(DPF) The DOC reacts with exhaust gases to reduce the carbon monoxide, hydrocarbons and some particulate matter(PM). The downstream DPF traps and holds the remaining PM, which are oxidized within the DPF through a continuous process called passive regeneration.

Rent the MMG 130 by calling 270.678.1712 or visiting NPM Services

Features

Reliable

  • Voltage regulation is plus or minus 1%
  • 342 gallon fuel capacity standard for 44 hours of run time
  • Air filter condition indicator on control panel
  • 2 year – 2,000 hour warranty
  • Low coolant shutdown

Durable

  • White aluminum textured powder coat enclosure, sound attenuated baffles and insulation to reduce noise, 68 dBA at prime
  • Fully lockable enclosure with stainless steel exterior hardware
  • Industrial strength steel skid frame and dual axle trailer
  • Central lift structure and convenient ladder on center of generator

Microprocessor Controlled for Safety

  • Engine & generator protection with our advanced Magnum Digital Controller (MDC
  • Fuel pressure monitoring
  • Oil pressure monitoring
  • Coolant monitoring
  • Battery voltage monitoring
  • Gen voltage monitoring
  • Overspeed monitoring
  • Over/under current monitoring
  • Generator over/under frequency monitoring

Easy to Use

  • Voltage selector switch (single phase & two 3-phase)
  • Electronic governor
  • Lugs and lug box safety switch, if cover is opened circuit breaker is tripped
  • Several convenience outlets with individual breakers
  • Durable external emergency E-stop switch
  • External fuel fill with lockable cap
  • Automatic remote start capable, located on control panel

Specifications

Output Pending CSA

3 Phase – Standby kW (kVA) 107 (134)
Amps 480V (208V) 161 (372)
3 Phase – Prime kW (kVA) 98 (122)
Amps 480V (208V) 147 (339)
1 Phase – Standby kW (kVA) 96 (96)
Amps 240V 400
1 Phase – Prime kW (kVA) 90 (90)
Amps 240V 374
AC Voltage 1-phase 120, 139, 208, 220, 240, 277
AC Voltage 3-phase 208, 220, 440, 480
Frequency Hz 60
Power Factor 1.0 (1 Phase) / .8 (3 Phase)
Generator – Brand / Type / Insulation Marathon / Brushless / H
Sound (dB(A) 23 ft @ prime)

Size and Weight

Skid Mounted – L x W x H in (m) 144 x 50 x 77
Dry Weight lbs (kg) 5444 (2469)
Operating Weight lbs (kg) 7929 (3596)
Trailer Mounted – L x W x H in (m) 210 x 86 x 93
Dry Weight lbs (kg) 6840 (3102)
Operating Weight lbs (kg) 9325 (4230)

Engine

Type Interim Tier IV
Brand John Deere PE4045HFG93
Aspiration Turbo
Power – Prime @ 1800 rpm hp (kWm) 152 (113)
Displacement cubic in (L) 275 (4.5)
Cylinders 4
Speed rpm 1800
Fuel Consumption – Prime gph (Lph) 7.4 (28.0)

Capacities

Fuel Tank gal (L) 342 (1295)
Approximate Run Time hrs 44
Coolant qt (L) 31.5 (29.8)

Electrical Distribution

Battery – 12V 1 – 12V 1000 CCA
Main Circuit Breaker Size A 450
Voltage Selection 3 Position Switch (lockable)
Voltage Regulation +/-1%
120V – 20A GFI Duplex Outlets – qty 2
240V – 30A Twist Lock Outlets – qty N/A
240V – 50A Twist Lock Outlets – qty 3

Trailer

Number of Axles 2
Capacity – Axle Rating lbs (kg) 6000 (2722)
Tire Size in 16
Brakes Surge
Hitch 3″ Ring
Maximum Tire Pressure psi 75

Comments are closed