MMG 480 Mobile Generator

The MMG480 diesel generator provides everything you need for auxiliary power in a mobile or skid generator. From battery charger to liquid containment, its all inclusive!

EPA Compliant Interim Tier 4 Engine

A powerful Interim Tier 4 Deere engine provides up to 419kW three phase power output ideal for oil and mining sites.

Rent the MMG 480 by calling 270.678.1712 or visiting NPM Services

Specifications

Output

3 Phase – Standby kW (kVA) 419 (524)
Amps 480V (208V) 630 (1454)
3 Phase – Prime kW (kVA) 379 (474)
Amps 480V (208V) 470 (1316)
1 Phase – Standby kW (kVA) N/A
Amps 240V N/A
1 Phase – Prime kW (kVA) N/A
Amps 240V N/A
AC Voltage 1-phase N/A
AC Voltage 3-phase 208, 480
Frequency Hz 60
Power Factor 0.8 (3 phase)
Generator – Brand / Type / Insulation Marathon, brushless H
Sound (dB(A) 23 ft @ prime) 68

Size and Weight

Skid Mounted – L x W x H in (m) 175 x 60 x 96
(4.45 x 1.52 x 2.44)
Dry Weight lbs (kg) TBD
Operating Weight lbs (kg) TBD
Trailer Mounted – L x W x H in (m) 250 x 102 x 116
(6.35 x 2.59 x 2.95)
Dry Weight lbs (kg) TBD
Operating Weight lbs (kg) TBD

EngineInterim Tier 4

Type
Brand Deere RG6135HFG95
Aspiration Turbo
Power – Prime @ 1800 rpm hp (kWm) 571 (426)
Displacement cubic in (L) 824 (13.5)
Cylinders 6
Speed rpm 1800
Fuel Consumption – Prime gph (Lph) 28.4 (107.6)

Capacities

Fuel Tank gal (L) 616 (2332)
Approximate Run Time hrs 20
Coolant qt (L) 95.5 (90.4)

Electrical Distribution

Battery – 12V 2 -12V (24V) 1000CCA
Main Circuit Breaker Size A 1600
Voltage Selection Link/Reconnect Board
Voltage Regulation +/-1%
120V – 20A GFI Duplex Outlets – qty 2
240V – 30A Twist Lock Outlets – qty N/A
240V – 50A Twist Lock Outlets – qty 2

Trailer

Number of Axles 3
Capacity – Axle Rating lbs (kg) 8000 (3629)
Tire Size in 17.5
Brakes Electric
Hitch 3″ ring
Maximum Tire Pressure psi 125